Frequently Asked Questions

Frequently Asked Questions

The UltraSense Platform

What is UltraSense?

UltraSense™ is a modular environmental monitoring and early-warning notification platform from Fireaway Inc., the manufacturer of Stat-X® condensed aerosol fire suppression. A networked base unit is paired with the sensors each site requires, selected from more than 80 available sensor types, including thermal imaging, flammable gas, temperature and humidity, power quality, vibration, leak, dust, and corrosion sensors, and reports the data to your monitoring, building management, or control systems.

UltraSense is used to identify the conditions that precede equipment failure and fire, such as overheating connections, battery off-gassing, or a flammable gas release, so that operators can act before a fire starts. It is deployed in battery energy storage systems, switchgear and power distribution equipment, data centers and network rooms, and solar and wind installations.

See our Products and Applications pages.

How is an UltraSense system built and expanded?

An UltraSense system starts with a base unit that connects to your network over standard 10/100 Mbps Ethernet and can be powered over Ethernet (PoE). Sensors connect to the base unit with standard RJ45 cabling at distances up to approximately 100 m, and sensor hubs expand the number of connected sensors.

Daisy-chain sensors, such as distributed temperature and infrared spot sensors, are wired in series along busway, cable runs, or racks from a single starter unit. Wired and wireless configurations are supported, so a system can begin with a few sensors on one enclosure and grow to a facility-wide installation without replacing the original equipment.

UltraSense also offers monitoring software that runs on your own systems. Talk to an UltraSense representative to design a custom solution.

How does UltraSense connect to my existing monitoring, BMS, or SCADA systems?

UltraSense natively supports SNMP, Modbus TCP, and MQTT, with optional expansion for Modbus RTU over RS-485. This allows the same sensor data to be read by network monitoring systems, building management and automation systems, industrial control systems and PLCs, and industrial IoT platforms.

Alerts can be delivered by email, SMS, and SNMP trap, and the base unit and optional relay output module provide dry-contact outputs for sirens, ventilation, load shedding, equipment shutdown, or inputs to fire alarm panels, as configured by the operator. See the Power Distribution page for an overview of integration in electrical facilities.

Are UltraSense components safety listed?

Yes. UltraSense sensors have been safety tested by UL to the UL 61010 standard for electrical equipment for measurement, control, and laboratory use, and base units and hubs meet UL 62368, the safety standard for information and communication technology equipment. The Flammable Gas Sensor is additionally ETL listed to UL 2075, the standard for gas and vapor detectors and sensors, and carries California State Fire Marshal listing CSFM-5275, CE marking, and EN 50270 and EN 61010 certification. Fireaway operates under ISO 9001:2015 and ISO 14001:2015 certified management systems.

The UltraSense Flammable Gas Sensor

What does the UltraSense Flammable Gas Sensor detect?

The UltraSense Flammable Gas Sensor (Part No. ULT-R-GAS-FLAMMABLE) detects and measures flammable gas concentrations from 0 to 100 percent of the lower explosive limit (%LEL) using a spectrometer-based sensing method, with a response time (T90) of less than 30 seconds.

It measures 11 gases: hydrogen (H2), methane (CH4), ethane (C2H6), propane (C3H8), propylene (C3H6), butane (C4H10), isobutane, pentane (C5H12), octane (C8H18), toluene, and xylene, with accuracy of ±5 %LEL for most gases. The sensor also reports a volatile organic compound (VOC) index, internal temperature, and relative humidity.

The combination of VOC and flammable gas measurement allows the sensor to indicate the first venting of a lithium-ion cell before hydrogen reaches a hazardous concentration. Full specifications are in the datasheet.

What is %LEL, and how are alarm thresholds set?

The lower explosive limit (LEL) is the lowest concentration of a gas in air that can ignite. Reporting in %LEL expresses how close the atmosphere is to that limit, so 100 %LEL for hydrogen (4% by volume in air) means an ignitable mixture.

The Flammable Gas Sensor does not have fixed alarm points. Warning and alarm thresholds are configured in the base unit for each sensor, and the sensor’s three normally open relays, two alarm relays and one fault relay, each rated up to 0.5 A, switch when those thresholds are reached or when the sensor detects a fault.

Thresholds are selected by the operator on the basis of the hazard analysis, the ventilation design, and the applicable codes for the facility, such as NFPA 855 for energy storage systems.

Does the Flammable Gas Sensor require calibration?

The Flammable Gas Sensor is calibration free. Unlike conventional catalytic bead and single-channel LEL sensors, which typically require calibration at six- to twelve-month intervals, the spectrometer-based sensing element does not drift in a way that requires periodic recalibration with reference gas.

Fireaway does recommend a periodic bump test in critical environments, in which a challenge gas is passed over the sensor to confirm that it responds. A bump test adapter (ULT-AX-GAS-BUMP) is available for this purpose. The sensor has a life span of up to 10 years on the hydrogen channel and up to 5 years on the methane channel.

How is the Flammable Gas Sensor installed and powered?

The sensor is powered from 12 to 24 V DC and draws between 678 and 1,400 mW. It communicates over Modbus RTU (RS-485), with addressing set by a 256-position rotary encoder, or connects directly to an UltraSense base unit over RJ45.

The industrial-grade steel enclosure measures 71 × 70.5 × 30 mm (2.79 × 2.77 × 1.18 in) and weighs 193 g (0.43 lb), and it can be mounted on a DIN rail, in a 0U rack position, magnetically, or on a wall. Operating range is −40 °C to 75 °C (−40 °F to 167 °F) at up to 95% relative humidity, non-condensing.

For lighter-than-air gases such as hydrogen, the sensor is mounted high in the enclosure or room, and a cone collecting adapter (ULT-AX-GAS-CONE) is available to improve capture. An IP65 protection box (ULT-AX-BOX-IP65) is available for dusty or damp locations. The sensor is designed for nonhazardous (unclassified) locations.

Where is the Flammable Gas Sensor used?

The most common application is early detection of off-gassing in lithium-ion battery energy storage systems, where hydrogen and VOC release precedes thermal runaway.

The same sensor is used in battery rooms for lead-acid and lithium-ion standby batteries, in UPS and telecommunications battery spaces, in EV charging and fleet depots, in solar and wind power electronics enclosures where battery storage is present, and in any unclassified facility where a flammable gas release is a credible hazard.

It is the Stage 2 (off-gas detection) and Stage 3 (thermal runaway detection) sensor in the UltraSense three-stage framework for energy storage. See Battery Energy Storage Systems and Clean Energy.

Applications

Which applications does UltraSense address?

UltraSense is not limited to battery storage. Application pages are available for:

These are grouped under three industry pages: Clean Energy, Power Distribution, and Critical Infrastructure.

What does UltraSense monitor in switchgear, transformers, and busway systems?

In switchgear, thermal imaging and infrared spot sensors continuously monitor connections, breakers, and bus bars for hot spots, and environmental sensors track humidity, water leaks, dust, vibration, and corrosion, which degrade insulation over time. This continuous condition monitoring supports the electrical maintenance programs described in NFPA 70B.

In transformers, UltraSense detects thermal anomalies, vibration that can deteriorate insulation, ozone generated by electrical discharge as insulation breaks down, and oil or water leaks. In busway systems, daisy-chained temperature sensors placed at joints and along trunking give continuous, real-time temperature monitoring of the connections most likely to fail. See Switchgear, Transformers, and Busway.

How does UltraSense support data centers and network rooms?

UltraSense monitors the conditions that cause downtime in data center white space, colocation rooms, edge data centers, and IDF, MDF, and network rooms:

  • Temperature and humidity at rack level for hot-aisle and cold-aisle management
  • Airflow and air pressure
  • Dust and particles
  • Corrosive gases and corrosion
  • Water leaks
  • Power quality
  • Door and motion status

The data help operators keep environments within the ASHRAE thermal guidelines for IT equipment and identify problems before they cause equipment failure. In data center white space and server rooms, UltraSense monitoring is Fireaway’s primary solution, while Stat-X fire suppression is applied to enclosed ancillary equipment such as electrical rooms, UPS and battery rooms, and generator enclosures. See Data Center White Space and IDF, MDF, and Network Rooms.

What does UltraSense detect in energy storage, solar, and wind installations?

For battery energy storage, UltraSense follows a three-stage approach:

  • Stage 1 monitors the operating environment (temperature, humidity, airflow, water leaks, and power quality) to prevent the conditions that stress batteries.
  • Stage 2 detects off-gassing at the first venting of a cell using VOC and flammable gas sensors.
  • Stage 3 detects thermal runaway using flammable gas, thermal imaging, and temperature sensors.

For solar installations, UltraSense monitors panel and inverter temperatures, dust accumulation, humidity and corrosion, and power quality and grounding effectiveness in inverter and combiner enclosures. For wind turbines, sensors inside the nacelle monitor vibration, gearbox and generator temperatures, humidity and corrosion, hydraulic fluid leaks, and electrical surges associated with lightning strikes.

See Clean Energy, Solar Installations, and Wind Turbines. For background on how battery systems fail, see BESS Failure Causes—Probably Not What You Think.

UltraSense and Stat-X

How do UltraSense and Stat-X work together?

Fireaway’s approach is prevent, detect, suppress. UltraSense provides the prevention and detection stages by monitoring equipment condition and identifying developing hazards, and Stat-X provides the suppression stage if a fire occurs.

Sensor data flows from UltraSense to the operator’s monitoring or control system, which can initiate alarms, ventilation, load shedding, or equipment shutdown, and can provide an input to the fire alarm and releasing control panel that controls the Stat-X system. Because Stat-X aerosol generators are compact and non-pressurized and require no piping, they are installed inside the same enclosures that UltraSense monitors: battery containers and cabinets, switchgear and control cabinets, transformer and inverter enclosures, and wind turbine nacelles.

Learn about Stat-X at statx.com and on the Stat-X FAQ page.

Can UltraSense automatically release a Stat-X system?

UltraSense sensors and base units provide relay outputs and network alerts that can be used as inputs to a fire alarm and releasing control panel. Release of a fixed fire suppression system is performed by that listed control panel, in accordance with NFPA 72 and NFPA 2010 or the equivalent local codes, and the panel determines the release logic, time delay, and abort functions.

In this arrangement, UltraSense supplies early-warning notification of off-gassing or overheating, allowing the operator to intervene before fire develops, while the fire detection and releasing system remains responsible for suppression release. How the two are combined is determined during system design, as configured by the operator and reviewed by the authority having jurisdiction.

How do I get started with UltraSense?

Start by describing the equipment and conditions you want to monitor. An UltraSense representative will help design a solution, from a single base unit and a few sensors for one enclosure to a networked system across a facility, and will recommend the base unit, sensors, and add-ons required. Visit Find Your UltraSense Representative, use the Contact page, or review the Products page for part numbers and datasheets.