  • Battery Energy Storage System (BESS) Failure Causes—Probably Not What You Think

    Battery Energy Storage System (BESS) Failure Causes—Probably Not What You Think

    Note to the reader: This article is intended solely for educational and informational purposes to discuss findings from the Electric Power Research Institute study on BESS failures. It does not, in any way—whether expressed, implied, or inferred—constitute an endorsement, approval, or sponsorship by EPRI of UltraSense™ or Stat-X® products.

    Introduction

    The Electric Power Research Institute (EPRI) is the world’s leading authority on tracking and analyzing incidents in BESSs and with their BESS Incident Database has established “the most comprehensive compilation of stationary BESS incidents.”

    In their 2024 white paper, Insights from EPRI’s Battery Energy Storage Systems (BESS) Failure Incident Database,  Analysis of Failure Root Cause, EPRI provided some highly interesting revelations into the rate of BESS failures, and more importantly, into the root causes of BESS failures.

    Currently, EPRI is the only publicly available database providing hard data on BESS incidents based on their root cause of failure. Determining the root cause of failure in BESS incidents is incredibly important to future BESS installations and for the protection of existing BESSs. Without this information, BESS installers, operators, and safety professionals are left guessing where to focus their efforts. Until the release of EPRI’s white paper, most had been looking in the wrong direction.

    EPRI Study Methodology

    It is important to first understand the parameters EPRI used in releasing their findings. The foundational component is their global BESS incident database which was established in 2021 after several high-profile BESS incidents in South Korea, as well as one in Arizona (USA) which injured several firefighters.

    Because BESSs are so widespread with myriad uses, EPRI concentrates only on events with commercial, industrial, or utility-grade BESS installations. To further refine their focus, EPRI defines a failure incident as an event that increases safety risk due to a BESS system or component malfunction, rather than from external factors such as a wildfires, storms, etc.

    Failure Classification

    BESS incidents can occur for many reasons. To better understand the data and draw accurate conclusions, EPRI used a two-pronged approach that divided the causes into (1) root cause and (2) failed element.

    Root Cause

    • Design
      A failure caused by flaws in the design, layout, or function of system components or the energy storage system (ESS) as a whole, including lack of safeguards against foreseeable misuse
    • Manufacturing
      A failure caused by a manufacturing defect in an ESS component, such as foreign material in cells, improper tolerances, or missing / misassembled parts
    • Integration, Assembly & Construction
      A failure resulting from poor integration, incompatible components, incorrect installation, or inadequate commissioning of the ESS
    • Operation
      A failure caused by system operation exceeding design limits—such as voltage, temperature, or state of charge—due to improper charging, discharging, resting behavior, or faulty sensing of critical parameters

    Failed Element

    • Cell / Module
      A failure originating in a lithium-ion cell or module—the core unit of the BESS—typically caused by internal short circuits leading to thermal runaway. Learn more here.
    • Controls
      A failure in the sensing, logic, or communication systems that manage ESS operation, including the battery management system (BMS), energy management system, and plant controllers; causes include system incompatibility, installation errors, defects, or improper operating limits
    • Balance of System (BOS)
      Failures involving the control or communication systems that govern ESS operation—such as the BMS, energy management, or plant controllers—often result from configuration errors, hardware faults, or improper operating limits.

    In their study, EPRI noted that some incidents had more than one root cause or failed element. In these cases, they were given more than one classification. An example they cited occurred in 2022 at the Elkhorn battery facility in Moss Landing, California (USA).

    In the aforementioned incident, rainwater ingress led to a short circuit in a battery cell which resulted in a thermal runaway. The rainwater ingress point was created and unnoticed during installation of another component. Compounding the problem, the loss-of-insulation alarm was not properly escalated until a fire occurred two days later.

    EPRI classified this event as involving both a construction-related issue within the BOS and a design-related issue in the control system.

    Results of the Study

    BESS Failure Rates

    The first interesting fact EPRI noted is that BESSs are becoming far safer. From 2018 to 2023, there has been an astonishing 97% decrease in the rate of utility-grade BESS failures. This is attributed to the maturity of the battery industry and R&D efforts to understand why BESS incidents were occurring and what measures could be taken to prevent or mitigate them.

    Since 2018, the number of BESS incidents has remained fairly static despite an enormous increase in the cumulative deployment of BESS installations.

    Root Cause Analysis

    Insufficient information from which to establish a root cause of failure is a common factor and impediment. For example, due to insufficient information, none of the nine incidents from 2011 to 2017 could be classified. However, from 2018 to 2023 twenty-six incidents were classified allowing statistically significant inferences to be made.

    The root causes of the aforementioned twenty-six BESS failures were as follows:

    • Integration, Assembly & Construction – Ten incidents / 36%
    • Operation – Eight incidents / 29%
    • Design – Six incidents / 21%
    • Manufacturing – Four incidents / 14%

    Note that two incidents had more than one root cause such as was mentioned previously.

    As “Integration, Assembly & Construction” was the leading root cause, the study revealed another interesting factor—most BESS failures, i.e., 72%—occur within the first two years of operation, including during or immediately following commissioning.

    The urban legend surrounding BESS failures is that manufacturing defects in lithium-ion batteries is the typical root cause of BESS incidents. The results of the study—with “Manufacturing” being solidly in last place of the root causes—clearly did not bear this out. This will be discussed further in the next section.

    Failed Element

    The failed element analysis also provided clear insight as to which component of a BESS was responsible for the incident. The results, which were surprising to many, are as follows:

    • Controls – Thirteen incidents / 46%
    • Balance of System (BOS) – Twelve incidents / 43%
    • Cells / Modules – Three incidents / 11%

    This information was stunning, as the accepted wisdom in BESS incidents is that cell failure as a root cause leads to thermal runaway. In fact, 89% of BESS incidents do not stem from battery failure. It should be noted however that battery failure / thermal runaway did occur in some incidents secondarily due to faults in the controls or BOS category. This will be explained in more detail in the following section.

    Cross-Referenced Analysis

    EPRI’s analysis of battery energy storage incidents examined both the initiating cause of each failure and the system component where it originated. When these two dimensions were compared, clear patterns emerged across the data set.

    The largest share of incidents involved issues related to construction and assembly of BOS components—such as cabling, cooling, or enclosure systems—where compatibility and workmanship were contributing factors. Events of this kind typically occur during installation or early operation, underscoring the importance of disciplined commissioning and verification procedures. Industry experience, including the 2021 Victoria Big Battery event in Australia, has shown that even minor assembly defects, such as coolant or water ingress, can escalate into significant failures.

    A second recurring theme across incident data relates to operational control systems. Several early-stage BESS events, particularly in Asia, highlighted the challenges of maintaining proper limits for voltage, temperature, and state of charge. These findings demonstrate that many failures arise from system management or operational boundaries rather than intrinsic cell defects.

    Beyond these categories, other reviews of public BESS data sets and field reports have noted that water intrusion remains a frequent contributor to electrical isolation loss and secondary thermal events. In some cases, this has been linked to leaks or design flaws in auxiliary systems, including fire-protection or HVAC components. Such examples illustrate the value of rigorous enclosure design, environmental sealing, and monitoring to reduce the likelihood of water-related faults.

    EPRI Conclusion & Recommendations

    The first notable conclusion in the EPRI study was that lithium-ion battery failure is not the prevailing cause of BESS incidents. In 89% of the cases, it is controls or BOS. This means that BESS operators and fire protection professionals need to rethink their approach to safety.

    Many of EPRI’s recommendations and mitigations focus on due diligence prior to installation and commissioning such as:

    • Following relevant codes and standards
    • Site-specific risk assessments
    • Selecting qualified suppliers
    • Strict specifications and quality assurance

    To protect the BESS during commissioning and operation, the focus turns to having a better understanding of what is going on inside of the BESS. EPRI highlighted the role of advanced sensing, monitoring, and data analytics in improving early detection of design or operational issues and in strengthening the predictive capabilities of battery management systems.

    While EPRI did not evaluate suppression methods, industry experience has shown that water-based fire systems can contribute to water ingress which has been shown to be a known factor in some BESS incidents.

    The Solution

    While EPRI’s findings do not reference or evaluate any specific products, they underscore the importance of sensing, monitoring, and suppression technologies—areas where commercially available solutions, such as UltraSense™ industrial sensors and Stat-X® fire suppression systems may play a role.

    These insights reinforce the practical reality that, despite improving safety trends, BESS incidents continue to pose serious challenges. Rapid escalation, difficult suppression, and extensive post-incident losses demonstrate why comprehensive protection strategies remain indispensable.

    Ideal protection for BESSs takes a three-pronged approach of:

    • Prevention
    • Detection
    • Suppression

    Prevention

    Many BESS failures are preceded by subtle environmental changes. Excessive heat or humidity, accumulating dust, vibration, or corrosive air quality can all be early indicators of impending problems. UltraSense’s advanced sensor technology monitors all of these conditions and provides the data needed to both optimize system performance and prevent failures.

    An effective prevention sensor suite addresses specific failure precursors:

    • High temperature—can lead to overheating or thermal runaway
    • High humidity—produces condensation and insulation breakdown
    • Dust and/or corrosive environment—undermines electrical insulation and cooling
    • Vibration—can cause mechanical failure

    By continuously monitoring these factors, operators can correct issues before they trigger failures.

    Detection

    Even though the preventative approach is most desirable, there are scenarios where failure may occur absent any of the conditions monitored by prevention sensors. In this case, early warning of developing issues is key to allowing intervention before conditions escalate.

    Again, UltraSense sensors and monitoring are the answer. An effective detection sensor array includes:

    • Water ingress which can cause short circuits leading to failure
    • Heat detection for developing hot spots on equipment or a rapid rise in enclosure temperature
    • IR thermography to detect even the smallest increase in equipment temperature
    • Volatile organic compound / hydrogen detectors (VOC/H2) which detect minute amounts of these gases produced when batteries first begin to fail, or insulation or other components significantly overheat
    • Flammable gas sensors detect the byproducts of thermal runaway
    • Smoke detectors (aspirating and photoelectric) provide early warning when smoke is produced during thermal runaway or a fire develops from another source

    Depending upon the configuration, detection sensors can trigger alerts to operators and/or automatically commence shutdown, cooling, or other interventions.

    Suppression

    While effective prevention and early detection sensors will mitigate most BESS incidents, operators should always prepare for the worst-case scenario of a fire. Rapid suppression of a developing fire can limit damage and downtime and exponentially increase the safety of those responding to the incident.

    Industry analyses, including data referenced by EPRI, have identified water intrusion as a contributing factor in several BESS incidents. Clean agent systems are expensive, in addition to being under intense scrutiny for health and environmental hazards. On the other hand, dry chemicals, while inexpensive and effective, are difficult to clean up and damaging to sensitive electrical components.

    Condensed Aerosol Generator

    As a result, condensed aerosol systems such as Stat-X are quickly becoming the first choice for BESS fire suppression. Stat-X has none of the downsides of the agents above, while also being more effective and easier / cheaper to install. Working in a total-flooding manner, Stat-X quickly extinguishes fire and remains suspended to provide reflash protection. It has been tested and proven effective on lithium-ion rack fires.

    Complementary Sensing & Fire Suppression Technologies

    Supplied from a single source, UltraSense and Stat-X technologies supply complementary protection with each enhancing the other’s effectiveness across sensing, detection, and suppression. This delivers an intelligent, cohesive, and coordinated approach to BESS safety.

    UltraSense offers a comprehensive suite of over 80 sensor types spanning thermal, environmental, electrical, and mechanical monitoring. This modular platform is specifically designed (and safety-certified) for BESSs, with the distinction of being the only listed, open & modular sensor platform focused on mitigating fire hazards in ESS / BESS deployments.

    Many UltraSense sensors are multi-functional—combining multiple sensing modalities in one unit—and can be daisy-chained for wide coverage with minimal wiring; this makes them well-suited to dense battery enclosures. The sensors are built for industrial durability and accuracy (e.g., ISO17025-calibrated temperature sensors), ensuring reliable performance in harsh conditions.

    When paired with Stat-X, this early warning capability becomes a full-spectrum protection strategy. Upon detection of fire conditions, UltraSense sensors can automatically activate the Stat-X fire suppression system. The enclosure is rapidly flooded with a fire-suppressing aerosol agent, stopping flame propagation and interrupting combustion at the chemical level.

    Further, since no piping or banks of agent are required, Stat-X is inexpensive to install and ideal for retrofitting. Being virtually maintenance free and having a 15-year service life, its lifecycle cost is exponentially lower than other systems. Stat-X has zero environmental or health risks.

    Conclusion

    EPRI’s study found that most BESS incidents stem from control systems or balance-of-system components—not battery cells. Its findings highlight the need for stronger design, commissioning, and monitoring practices to detect and prevent faults early and are intended to guide general industry practice.

    Across the energy-storage sector, early detection and rapid suppression remain critical to minimizing fire risk and downtime. Complementary sensing and suppression technologies can provide a coordinated defense by identifying abnormal conditions, triggering response actions, and limiting fire propagation. UltraSense sensors and Stat-X condensed-aerosol systems exemplify this layered approach; however, they are referenced here solely for illustrative purposes and are not endorsed or validated by EPRI.

  • Six Reasons to Use UltraSense™ Sensors

    Six Reasons to Use UltraSense™ Sensors

    In mission-critical environments—e.g., data centers, battery energy storage systems, and power-handling equipment—the best form of fire protection does not focus on fire suppression, but rather on fire prevention and detection. UltraSense™ sensors monitor for a variety of conditions which provide operators with early detection of anomalies, allowing them to intervene before a fire even starts. Further, they provide near-instant detection in the event of an actual fire.

    Following are six compelling reasons to deploy UltraSense sensors:

    1. Comprehensive Environmental Monitoring in One Unified Platform

    High ambient temperature, extreme humidity, or excessive dust can overheat equipment or cause malfunctions that lead to electrical faults and fires. UltraSense sensors provide atmospheric monitoring that covers all of these conditions. By understanding the environment where equipment is operating, users can take early action to prevent problems before they occur.

    UltraSense sensors deliver real-time data / alerts as to the following conditions:

    • Temperature
    • Humidity
    • Particulates in the air
    • Water ingress

    With this broad range, UltraSense enables centralized monitoring of environmental conditions. The need for piecing together multiple systems—which can lead to fragmented visibility and increased integration costs—is eliminated.

    2. Tailored for Harsh Environments

    Unlike many commercial-grade sensors which are designed for office settings, UltraSense sensors are ruggedly constructed for real-world applications.

    Many models feature:

    • Industrial temperature ranges (e.g., -40°F to +185°F)
    • Dustproof and waterproof enclosures
    • Electromagnetic shielding to reduce interference
    • Robust mounting options for equipment racks, ceilings, or walls

    For harsh and sensitive environments alike, UltraSense’s hardware durability is crucial. These sensors continue operating in hot, wet, corrosive, or dirty environments where lesser systems would fail.

    3. Efficient Deployment & Scalable Architecture

    UltraSense’s platform is modular and scalable, making it ideal for projects of all sizes. Whether monitoring one electrical cabinet or multiple sites, the architecture supports gradual, efficient rollout with features such as:

    • Modular base units which support multiple sensors
    • Wireless and wired sensor options for flexible deployments
    • Daisy-chaining support that extends coverage without excess cabling
    • Edge-capable—meaning they process data locally, unlike traditional sensors that simply transmit data to a centralized server or cloud

    The above features enable companies to expand sensor coverage without overhauling existing infrastructure. This reduces the total cost of ownership which is particularly important in budget-conscious sectors.

    4. Early Thermal Anomaly Detection

    UltraSense’s thermal sensors continuously monitor the heat conditions of equipment surfaces and operating environment. Even slight temperature increases can trigger alerts, enabling proactive inspection before a fault becomes hazardous.

    UltraSense sensors provide:

    • Dedicated temperature sensors deployed across critical areas to detect minute increases in room or surface temperature which inform operations and maintenance personnel
    • High-resolution IR thermography which scans equipment surfaces in real-time, visually mapping heat distribution to detect abnormal thermal patterns and hot-spots
    • Integration with edge-capable controllers which automatically analyze thermal data on-site and issue alerts when a preset temperature threshold is breached

    By combining continuous ambient monitoring with real-time IR hot-spot detection and smart edge-triggered alerts, UltraSense provides an early-warning framework to identify potential fire sources before it begins.

    5. Off-Gas Monitoring for Quick Detection

    Many issues that lead to fire begin with off-gassing vapors well before visible fire has formed. UltraSense provides VOC/H2 (volatile organic compound and hydrogen) gas sensors which detect abnormal emissions from batteries, electronics, or machinery, alerting operators before smoke activates traditional alarms.

    UltraSense gas monitors:

    • Can detect minute emissions of VOCs released from overheating components
    • Detect the presence of hydrogen—which is a strong indicator of potential fire risk—in battery energy storage systems
    • Provide fast response times (<30 seconds) and high accuracy (±3% LEL)

    By identifying early-stage chemical emissions with precision and speed, UltraSense gas monitors serve as a critical first line of defense against fire, enabling proactive intervention before conditions escalate into visible flames or system failures.

    6. Virtually Instant Fire Detection

    If conditions deteriorate before preventive measures can be taken, UltraSense also provides aspirating and photoelectric smoke sensors. These sensors complement thermal and gas monitoring in a layered defense.

    With a full suite of UltraSense sensors, users can become almost instantly aware of fire through:

    • Smoke detection
    • Heat detection
    • Gas detection
    • IR thermography

    Using UltraSense’s multi-tiered setup—spanning smoke, heat, gas, and IR thermography—operators gain near-instant awareness of fire conditions allowing prompt intervention before conditions escalate.

    Conclusion

    UltraSense sensors create a proactive shield against fire by providing early warnings at every stage, ranging from heat anomalies to water ingress and smoke. Their layered, edge-based, and integrated approach ensures that instead of relying on fire suppression, fires are prevented before they begin. In a world where downtime is costly and environmental risks are rising, smart monitoring is mission-critical. UltraSense sensors offer the breadth, intelligence, and resilience needed to stay ahead of problems.